CVE-2025-2520
HIGHDescription
The Honeywell Experion PKS contains an Uninitialized Variable in the common Epic Platform Analyzer (EPA) communications. An attacker could potentially exploit this vulnerability, leading to a Communication Channel Manipulation, which results in a dereferencing of an uninitialized pointer leading to a denial of service. Honeywell recommends updating to the most recent version of Honeywell Experion PKS: 520.2 TCU9 HF1and 530.1 TCU3 HF1. The affected Experion PKS products are C300 PCNT02, EHB, EHPM, ELMM, Classic ENIM, ETN, FIM4, FIM8, PGM, and RFIM. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3.
CVSS v3 Vector
Exploitability
Impact
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Exploit Intelligence
Low risk: more likely to be exploited than 28% of all known CVEs.
References
Find and fix vulnerabilities across your fleet
TridentStack Control continuously scans your Windows, macOS, and Linux fleet for known vulnerabilities, prioritizes them by severity and active exploitation, and patches them automatically.
Start freeThis product uses NVD data but is not endorsed or certified by the NVD. EPSS scores courtesy of FIRST.org (https://www.first.org/epss). Source: CISA KEV Catalog. Data as of 2025-07-15.