CVE & CISA-KEV Catalog

CVE-2026-3611

CRITICALEPSS 92th pctl
10.0
CVSS v3
NVD

Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

CVSS v3 Vector

Exploitability

Attack VectorNetwork
Attack ComplexityLow
Privileges RequiredNone
User InteractionNone
ScopeChanged

Impact

ConfidentialityHigh
IntegrityHigh
AvailabilityHigh

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

Exploit Intelligence

5.58%probability of exploitation in 30 days
92ndpercentile

High risk: more likely to be exploited than 92% of all known CVEs.

References

Find and fix vulnerabilities across your fleet

TridentStack Control continuously scans your Windows, macOS, and Linux fleet for known vulnerabilities, prioritizes them by severity and active exploitation, and patches them automatically.

Start free

This product uses NVD data but is not endorsed or certified by the NVD. EPSS scores courtesy of FIRST.org (https://www.first.org/epss). Source: CISA KEV Catalog. Data as of 2026-06-05.